Crown Boiler WWD224W-2 Spezifikationen

Stöbern Sie online oder laden Sie Spezifikationen nach Wasserspender Crown Boiler WWD224W-2 herunter. Crown Boiler WWD224W-2 Specifications Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 13
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
1
WaterMax
SUPER SPORTS TURF PUMP STATION
Variable Frequency Drive Control System
GENERAL SPECIFICATIONS
Project Name: ?
Project Location: ?
Pumping System Model #: WaterMax SSTV-HP-Voltage-Phase-Flow-Boost
Total Design Criteria: Quantity of Pumps: ?
Station Design Capacity: ? GPM @ ? PSI Discharge
08/22/06
SCOPE OF WORK
It is the intention of this specification to describe an automatic, prefabricated, self-enclosed, pump station for
irrigation purposes. Design, fabrication, testing and service shall be the sole responsibility of the pump station
manufacturer. The pump station shall provide water to the irrigation system while simultaneously maintaining
a constant discharge pressure by using a prefabricated pump station with variable frequency drive (VFD)
pumps for pressure regulation, under varying flow conditions up to the maximum specified capacity.
Construction shall include a fabricated steel plate and skid assembly to support all components during
shipping and to serve as the installed mounting base.
SECTION 1: GENERAL
1.1 The prefabricated pumping station shall have a minimum capacity and discharge pressure at skid
edge as stated in the technical specifications.
1.2 The station shall be completely wired, piped, hydraulically and electrically tested prior shipment.
1.3 The discharge manifold from the pump station shall terminate at or near the pump station skid edge
and be provided by the pump station manufacturer.
The pumping station shall be model number WaterMax SST as manufactured by WATERTRONICS, INC. 525
Industrial Drive, P.O. Box 530, Hartland, Wisconsin 53029-0530, www.watertronics.com
.
SECTION 2: MANUFACTURER REQUIREMENTS
2.1 MANUFACTURER
The pump station shall be manufactured by Watertronics Inc., Hartland, Wisconsin. The following information
must be furnished by the contractor or manufacturers representative:
a. A complete specification and submittal of all major components for the proposed pump
station with individual pump performance verification.
b. A detailed pump station proposal drawing complete with component location, sizes and
dimensions specific to the installation.
c. A complete electrical schematic for all high and low voltage circuits showing breaker/fuse
sizing, wire numbering and color.
d. Pump station manufacturers U.L. file number for the entire pump station.
e. A copy of the manufacturers certificate of insurance.
Seitenansicht 0
1 2 3 4 5 6 ... 12 13

Inhaltsverzeichnis

Seite 1 - WaterMax

1 WaterMax SUPER SPORTS TURF PUMP STATION Variable Frequency Drive Control System GENERAL SPECIFICATIONS Project Name: ? Project Location:

Seite 2

10 SECTION 9: PAINTING (steel enclosure) Painting of the entire unit shall consist of a multi-step coating system which includes metal preparation,

Seite 3

11 12.4 Discharge Drop Pipe (Optional; must be called for in the Technical Specification) The pump station manufacturer shall supply the discharge

Seite 4

12 Touch Screen Operator Interface and include a run light, HOA switch and speed pot. In manual mode, the user can manually adjust pump speed. A Cl

Seite 5

13 9.4 Chemical Storage Tanks (Optional; must be called for in the Technical Specification) Scope: Pump system manufacturer shall provide the fo

Seite 6

2 SECTION 3: PUMPS AND MOTORS 3.1 PUMPS Pumps shall be electric motor driven, horizontal centrifugal with mechanical shaft seal, volute case and

Seite 7

3 - A wash-down 3/4" brass hose bib shall be provided downstream of the control valves, upstream of the main station isolation valve 4

Seite 8

4 d. Adjustable pressure ramp-up and ramp-down to assure surge free pressure regu

Seite 9

5 monitoring and control purposes. The PLC shall contain two communication ports for monitoring and programming purposes. The PLC shall contain an EE

Seite 10

6 e. Alarm status with time stamping, display of pump station conditions at shutdown and restart. Alarms will be displayed in red when activat

Seite 11

7  System status: System O.K. or System Pressurizing  Seven, (7) different pressure regulation points based on seven different user definable GPM

Seite 12

8  The data and the user given description is then also available in the PumpLink. OCX utility for use by any irrigation equipment company’s softwa

Seite 13

9 5.14 PHASE MONITOR The incoming power and each motor shall be protected by a phase loss/low voltage system dropout relay to de-energize the pump